VAPOPREX LVP
- Steam output from 150 to 3000kg/h
VAPOPREX LVP
- Steam output from 150 to 3000kg/h
- Low pressure steam boiler with three flue passes, two in furnace.
Low pressure saturated steam generator with flame inversion, monobloc, in steel with pressurized combustion and high energy efficiency. Designed to operate in combination with a blown air burner with liquid or gaseous fuel. Flame inversion furnace and combustion chamber with wet bottom and sized to ensure low thermal loads.
Range consisting of 7 models with useful powers from 1,006 kW to 2,682 kW.
-
Technical Data
• Standard design pressure 1 bar.• Steam production from 1,500 to 4,000 kg/h (up to 2,000 kg/h of steam, completely exempt from the requirement of a licensed operator).
• The door is fixed to the tube plate by means of hinges and is internally lined with an adequate thickness of refractory cement which covers the entire heated surface of the plate itself.
• Generously sized evaporating chamber with a large exchange surface for the production of high quality saturated steam.
• Dispersals towards the environment are very limited thanks to adequate insulation of the boiler body carried out with a layer of high-density mineral wool and without thermal bridges, protected by a stainless steel sheet (AISI 430).
• The welding of the pressurized parts is all carried out by qualified and IIS approved personnel according to EN standards.
• Modern in design and high efficiency, these generators are designed and manufactured in compliance with the European Directive 2014/68/EU (PED) and the most recent national and European standards regarding pressure vessels.
• Inspection on the water side is guaranteed by a manhole on the top of the boiler and a handhole in the lower part.
CERTIFICATIONS
CE marking according to the Directives
Pressure vessels (2014/68/EU)
Low Voltage (2014/35/EU)
Electromagnetic Compatibility (2014/30/EU)
ACCESSORIES ON REQUEST
• Economizer : it is a water-fume heat exchanger that allows for an increase in efficiency of around 4%. Its configuration and positioning are carried out according to the customer's needs.
• Ladder and walkway for safe access to the walkable platform above the boiler.
• Modulating power supply system with pump and inverter for optimal management of the water level in combination with an economizer.
• Burner : brand and type according to customer specifications.
• Burner plate perforated according to customer specifications.
• Second stand-by fuel pump with valves.
• Second level indicator with taps.
• System for automatic bottom drainage of sludge and dissolved salt deposits.
• Salinity control system (TDS) for the detection of dissolved salts in the operating water.
• Cooling barrel for sampling boiler water.
• BMS 24H for continuous unsupervised operation for up to 24 hours.
• BMS 72H for continuous unsupervised operation for up to 72 hours.
• Second minimum level probe FAIL SAFE.
• FAIL SAFE maximum level probe.
• “MODULE F” certification.
• The control system consists of a PLC equipped with a high-performance color Touch Panel operator interface. The interface allows you to supervise the operation of the Boiler-Burner-System assembly.
• VRC condensation collection vessel.
• VRD atmospheric degasser.
• “BDV” drain cooler tank.
• Water treatment system.
• Steam collector.
• Staircase with walkway.
-
Brochure